PSC-PWM tuning

PSC-PWM is the as-built default modulator (see modulators) and was bench-validated at 5 kHz with both bridges thermally matched. This roadmap item covers further tuning beyond what was demonstrated.

What's already in place

Status
90° carrier phase shift between TIM8 and TIM1 Working — lock=OK reported consistently
Carrier-phase lock diagnostic (g_pwm_measured_cnt_offset + g_pwm_phase_locked) Published on every $C,...,cntoff=N,lock=OK\|BAD config line
Runtime switching-frequency sweep via FSW UART command 100 Hz – 20 kHz allowed
Hard fallback to STAIR_ALT if PSC lock=BAD Operator-selectable from dashboard
Bench validation at 5 kHz Five distinct cascade levels at 100 V, bridges thermally matched within ≈ 3 °C

What this item covers

Switching-frequency sweep

A structured sweep across the firmware's allowed FSW range (100 Hz to 20 kHz) to characterise the tradeoffs:

fsw What changes
Lower (≤ 1 kHz) Lower switching loss; lower thermal load; output ripple becomes audible / larger; LC filter needs to be bigger
Headline 5 kHz Bench-validated; balance of loss + filter size
Higher (≥ 10 kHz) Switching loss climbs (dead time becomes a larger fraction of period); ripple energy moves up where smaller LC filters work; gate-loop parasitics become more important to control

Deliverables: per-frequency measurement of cascade-output THD (pre-filter), bridge case-temperature delta, gate-loop ringing on the scope. A 5-point sweep (500 Hz, 1 kHz, 5 kHz, 10 kHz, 20 kHz) of 5 minutes per point would be a one-session experiment. Telemetry replay from each run is in the dashboard's replay format.

Carrier-phase offset sweep

The PSC carrier phase shift is currently fixed at 90° (TIM8 CNT preset to ARR/2). For 2 cells this is textbook-optimal — phase shift = 360°/N = 180° for 2 cells, but unipolar modulation uses half that = 90°. The roadmap question: does fine-tuning the phase by a few degrees give measurable improvement under partial bridge mismatch (e.g. different supply rails, different MOSFET binning)?

Implementation hint: add a runtime PHASE <offset_ticks> UART command that adjusts the TIM8 CNT preset away from ARR/2. The lock-detection logic then checks cntoff against the new target, not against ARR/2. Tunable by sweep, measurable by FFT.

Closed-loop carrier lock

Today, if lock=BAD is reported, the operator manually falls back to STAIR_ALT. A closed-loop variant would have the firmware:

  1. Detect lock=BAD after every config change.
  2. Auto-retry the phase-shift application up to N times.
  3. If still bad, auto-select STAIR_ALT and emit a UART notification.

Implementation hint: a few additional state transitions in fsm.c plus a counter. No hardware change.

Effort estimate

Sub-item Engineer-time
Switching-frequency sweep + write-up 1 day bench + 1 day analysis
Phase-offset sweep 1 day bench + 1 day analysis (requires the runtime PHASE command)
Closed-loop carrier lock 2 days firmware + bench verification

Why this matters

The carrier-shift lock=OK\|BAD diagnostic was added defensively before the first bench session — it caught a real issue immediately (iteration-4). Extending it to auto-recovery and adding structured sweep data is the next step in making PSC robust enough to ship in any product version of this design.