Protection

Four protection conditions are checked after every 1 kHz sensor scan. Each has its own N-of-M debounce counter — a fault must hold for 3 consecutive scans (3 ms) before it trips.

Conditions

Bit Name Trip condition Default threshold
0x01 UV DC bus < UV threshold 40 V (at VNOM = 50 V)
0x02 OV DC bus > OV threshold 58 V (at VNOM = 50 V)
0x04 OC Iout
0x08 IMBAL Vdc1 - Vdc2
0x10 SENSOR_LOST Required sensor stuck at rail — (latches when detected)
0x20 MANUAL Operator TRIP command —

Runtime-tunable thresholds (VNOM)

The DC-bus thresholds (UV, OV, IMBAL) are not fixed — they scale with a single runtime-set nominal bus voltage so the inverter can be bench-tested below the 50 V design point without UV firing immediately.

  • VNOM <v> sets the nominal per-bridge bus voltage, 5–60 V.
  • The firmware derives:
    • UV = 0.80 × VNOM
    • OV = 1.16 × VNOM
    • IMBAL = 0.20 × VNOM

At VNOM = 50 these reproduce the original 40 / 58 / 10 V design values. At VNOM = 12 (a typical bench supply) they become 9.6 / 13.92 / 2.4 V — so low-voltage testing actually leaves PRECHARGE without an instant UV trip.

Overcurrent (OC) is independent of VNOM because it is a load property, not a bus property — set it separately with OC <amps> (0.5–20 A).

The active protection config is reported on the $P line, emitted at boot, on any VNOM/OC change, and on CONFIG:

$P,vnom=12.00,uv=9.60,ov=13.92,oc=15.00,imbal=2.40

Sensing modes and per-mode protection

ID Mode Sensors Active protection
0 FULL DC1, DC2, current UV, OV, OC, IMBAL
1 DC_ONLY DC1, DC2 UV, OV, IMBAL
2 CUR_ONLY Current OC
3 OPEN None None — emits a UART warning
4 DC1 DC1 (+ optional current) DC1 UV/OV + OC if available
5 DC2 DC2 (+ optional current) DC2 UV/OV + OC if available

At boot, each ADC is read four times. Sensors stuck at 0x000 or 0xFFF are marked unavailable and the FSM auto-demotes to the most capable supported mode (and emits $E,MODE_DEMOTED).

OPEN mode — explicitly unprotected

OPEN mode is allowed (for hardware where the sensors aren't yet wired) but emits $E,WARNING_OPEN_LOOP_NO_PROTECTION whenever it is selected or started. Auto-start still fires in OPEN mode — the standalone-demo use case is the reason the warning is a warning and not a block. The operator who deployed firmware in OPEN mode accepted the risk.

Fault path

When a debounced fault trips, the FSM:

  1. Forces BDTR.MOE = 0 on both TIM1 and TIM8. Outputs go to LOW via OSSI=1, MOSFETs off via TLP250 non-inverting.
  2. Latches the fault bit(s) in g_protection_latched.
  3. Pulls FAULT_OUT (PB5) LOW.
  4. Emits $F,<bits>,vdc1=<v>,vdc2=<v>,cur=<a> on UART.

The fault stays latched until CLEAR is sent and the active condition is gone. If the operator clears while UV is still active, the FSM re-evaluates and stays in FAULT.

Recovery

Situation Path
Fault triggered, condition cleared CLEAR → FAULT → IDLE → START
Fault triggered by sensor loss RESCAN (allowed in FAULT) → re-check sensors → CLEAR if recovered
Bench testing below 50 V VNOM <v> (allowed in FAULT) → CLEAR if UV/IMBAL was the trip → START
lock=BAD reported on $C for PSC MOD STAIR_ALT as hard fallback while debugging the carrier phase