State machine

The firmware is supervised by a 5-state FSM that owns the MOE-bit (PWM master output enable), sensor mode, and protection latch.

Diagram

stateDiagram-v2
    [*] --> BOOT
    BOOT --> IDLE: ADC self-test &
pick best mode IDLE --> PRECHARGE: START IDLE --> FAULT: sensor fault PRECHARGE --> RUN: g_precharge_done PRECHARGE --> IDLE: STOP PRECHARGE --> FAULT: UV / OV / OC / IMBAL RUN --> IDLE: STOP RUN --> FAULT: UV / OV / OC / IMBAL FAULT --> IDLE: CLEAR (after condition cleared)

What each state does

State MOE Behavior
BOOT 0 Hardware init, ADC self-test, sensing-mode auto-selection. Drops to IDLE.
IDLE 0 Both advanced-timer MOE bits low. Accepts all commands.
PRECHARGE 1 MOE on; PWM ISR forces low-sides ON for 6 ms (3 PWM periods at 500 Hz) to charge the bootstrap caps.
RUN 1 PWM enabled. Protection runs after every 1 kHz sensor scan.
FAULT 0 MOE forced off via BDTR.MOE = 0; fault bits latched; FAULT_OUT pin pulled LOW. Operator must send CLEAR after the underlying condition is gone.

The auto-start path is layered onto this: if no UART byte is received within 3 s of FSM_Init(), the FSM issues its own START and emits $A,AUTO_START. Sending any UART byte during the window cancels auto-start permanently for that boot cycle.

Sensing modes (per-mode protection)

ID Mode Sensors used Active protection
0 FULL DC1, DC2, current UV, OV, OC, imbalance
1 DC_ONLY DC1, DC2 UV, OV, imbalance
2 CUR_ONLY Current OC
3 OPEN None None — emits a UART warning
4 DC1 DC1 (+ current if available) DC1 UV/OV + OC if current passed
5 DC2 DC2 (+ current if available) DC2 UV/OV + OC if current passed

At boot, each ADC is read four times; sensors stuck at 0x000 or 0xFFF are marked unavailable and the FSM auto-demotes to the most capable supported mode (and emits $E,MODE_DEMOTED).

Protection latch and CLEAR

A fault must hold for PROTECTION_TRIP_COUNT = 3 consecutive 1 kHz sensor scans before it trips — 3 ms total. Any clean read resets the counter. Once latched, the FSM:

  1. Forces BDTR.MOE = 0 (PWM outputs go to their inactive level via OSSI=1).
  2. Latches the offending fault bit(s) in g_protection_latched.
  3. Pulls FAULT_OUT LOW.
  4. Emits $F,... over UART.

CLEAR succeeds only when the underlying condition is gone. If the operator clears while UV is still active, the FSM stays in FAULT and re-emits $F.

Forced fault (TRIP)

Operator-issued TRIP latches FAULT_MANUAL (0x20) and runs the full fault path — useful for demonstrating the protection chain when sensors aren't readable.